Shaped Rooms & Hallways  (Available as a Printable PDF see downloads)

Shaped or Open Adjoining RoomsHall, Stairs & Landings

We can now use the table to ascertain what size heaters are required,

 

The Hall is to be No Less than 363 Watts

so this means we would use a 400 Watt heater.

 

The Landing is to be No Less than 319 Watts

so this means we would use a 320 Watt or 400 Watt heater.

 

So our heaters required to heat the whole area are,

 

Hall              

Landing        

 

1 x 700mm x 600mm

1 x 700mm x 600mm or 1200mm x 350mm

    

 

Landing

m3 + 6.5m3 = 14.5m3 x 22 = 319 Watts

 

Hallways, Stairs and Landing should be calculated by separately measuring each section,

 

Example:

 

Hall              

Landing        

Stairs

m3 + 6.5m3 = 14.5m3 x 22 = 319 Watts

 

We now have to divide the stairs m3 into 2, we do this so both the hall and the landing heaters will assist in the heating of the stairs.

 

13m3 / 2 = 6.5m3

 

We then add this total to both the hall & landing totals and calculate the heater required by multiplying them by our usual 22watts/m3,

 

Hall

 

If your room is not rectangular, L-Shaped for example then it should be divided into two sections.  Each section should then be calculated separately using the calculation on the previous page with each section having a heater installed.  This calculation should be used also if rooms are joined together by an open archway.

5.0m x 0.8m x 2.5m = 10m3

4.0m x 0.8m x 2.5m = 8m3

6.5m x 0.8m x 2.5m = 13m3

10m3 + 6.5m3 = 16.5m3 x 22 = 363 Watts

 

8m3 + 6.5m3 = 14.5m3 x 22 = 319 Watts

 